1. Heater Location
As near as possible to the place of use protected against frost and enabling easy dismantling of the heating element. The heater is fastened with two M8 screws.
Installation must be carried out according to the applicable regulation. In case the heater is situated above a residential area (e.g. in the attic), a tank should be situated at outlet.
FIXATION OF HEATER ON A WALL
Heaters 80 L
Heaters 150 L
2. Connection to the Water Main
The pressurized heater must be fitted with a safety device (i.e. a relief valve). ATLANTIC does not deliver safety devices. The relief valve must comply with the prescribed standard and must be situated as near the heater as possible. If pressure exceeds 5 bar, an upper pressure-reducing valve must be installed. This valve is installed right on the cold water inlet pipe with cast-iron or steel joints. Threads must be watertight. Carry out the installation according to the manufacturer’s instructions.
Outlet must be connected to a discharge circuit. The relief valve enables outflow of a part of water during heating when the volume of water is increasing, so that the inner pressure in the tank does not exceed 7 bar. Outflow is a normal phenomenon representing about 3 % of water volume in the tank. Before connecting the heater to the power supply, let water flow off several minutes to be free of all impurities that could endanger the functionality of the safety system. The heater is usually fitted with a special flow blender.
Warnings:
The hot water outlet may never get clogged. During heating, a small volume of water is running through the heater in dependence on the pressure in the tank. This phenomenon is quite normal.
3. Commissioning
Open hot water taps to discharge air from piping and fill the heater with water.
Make sure that
Guarantee in case of failure is only valid provided the installation has been carried out according to the applicable standards. During heating, the heater may make sounds, in dependence on the quality of water, as water being warmed up in a kettle. It is not a fault.


Fig. 3 - Mounting Diagram
Hot watter will be pressed up with cold watter of main pipeline
for 10 L heaters 2 - 4 m are necessary.
for 15 L heaters 4 - 8 m are necessary.
No valves can be installed in this areas.
RECOMMENDATIONS FOR USERS – MAINTENANCE
Discharge of the heater type “above a sink”, incrustation removal procedure:
a) Disconnect the electric power supply.
b) Close the cold water inlet.
c) Open the hot water tap.
d) Open the discharge valve.
The heater type “under a sink” must be dismounted for water discharge.
To ensure the correct function, THE SAFETY VALVE MUST BE TURNED QUICKLY TWICE A MONTH.
In case of defect – water is not warmed up or steam is released, e.g. when a pumping cock is open – disconnect the electric power supply and call a plumber.
In case of longer absence disconnect the power and water supply.
In case the heater is out of operation and it can get frozen, do not disconnect the power supply and set the thermostat on “mini”.
Guarantee Conditions
See the Claim Regulations .